Inspections

The Building Division administers the building permit process for both residential and commercial construction. This is a fundamental process for ensuring the protection of life and property.

The process begins with the submittal of plans and construction documents, which are reviewed for compliance with applicable Building Codes and Standards. Approved projects are issued a Building Permit allowing construction to begin.

The Building Division also conducts field inspections to ensure that the work covered by the permit is done according to the plans, and is in compliance with all Building Codes and City Ordinances adopted by the City of Oceanside. It shall be the responsibility of the owner or licensed contractor doing the work authorized by a permit to notify the Building Division when said work is ready for inspection. No portion of any building, structure, wiring, plumbing, ductwork or equipment, which is required to be inspected, shall be covered or concealed without approval of the Building Official or his Deputy. The inspection process culminates with a final inspection and the issuance of a Certificate of Occupancy.

Types of Required Inspections

Foundation/Footing

Location of the forms to meet zoning setback requirements, elevation of the forms to meet flood control requirements, depth and width of the footing, and proper placement, size and grade of reinforcing steel. All required shear wall anchor bolts, hold-down bolts, and straps are expected to be hung on templates. The UFER ground is checked for proper installation and location.

Slab

Thickness of the slab, placement of sand and vapor barrier, size, spacing and support of reinforcing bar.

Floor Framing

Size, spacing, grade, span, lap and support of floor joist and girders and clearance to grade. Rough plumbing, mechanical and electrical. Under floor ventilation and access.

Roof Sheathing Framing

Size, spacing, grade and span of rafters and purlins. Framing hardware, i.e., hangers, straps, etc. Structural supports, i.e., posts, beams, headers. Sheathing panel index, shear diaphragm, shear transfer. Plumbing and mechanical vents through the roof. Trusses, installed per plan, truss calcs available for inspector.

Prewrap

Location, panel index, size and nailing of shear walls. Hold-down hardware, shear wall anchor bolts, plate washers. Location and size of doors and windows. All windows must be installed to check for emergency egress, glazing and flashing.

Framing

All structural, rough plumbing, rough mechanical and rough electrical installations are checked at framing. Structural: size, spacing and grade of studs. Size, spacing, grade, span and support of joist. Cutting, notching and boring of studs, joists, and review interior shear walls.

Rough Plumbing

Drain, waste and vent piping capped or plugged outside the building and filled with water until vents overflow to test for leaks. Proper location of all fixture stud cuts as shown on floor plan. Drain and vent sizing, wet venting, slope and support of drain lines. Approved joints and fittings. Location and size of cleanouts. Protection from physical damage for non-metallic piping. Water piping: static pressure on lines. Proper material, location, size and supports.

Rough Mechanical

Proper material, size, location, support and installation of all duct work. FAU compartment: supply air (plenum), return air, combustion air and condensate drain line(s). Fire and draft stopping. Combustion vents: location and clearances.

Rough Electrical

General wiring to convenience outlets and lights. Grounding and bonding: metal boxes, cold water piping, grounding electrode conductor, neutral and grounding busses. Wiring/conduit locations: support and protection, GFCI and smoke detector circuits, laundry and kitchen circuits. Clearances at subpanels and service entrance equipment. Rated boxes in fire separations.

Insulation

Check for compliance with Title 24 Energy requirements: Insulation placement, windows, doors, plumbing pipes, and electrical wire holes are sealed.

Drywall

Proper type and thickness. Nail or screw spacing.

Lath

Kraft paper type, connection, and number of layers are per code requirements. All holes in Kraft paper are sealed.

Gas Test

After drywall has been placed, an air pressure test is required. The gas line must hold at a minimum of 10 psi for 15 minutes.

Electric Final

Prior to the final inspection, a final electrical Inspection is required to release the electric meter for testing. All wiring must be complete, all electric switches, plugs, lights, and cover plates must be installed. All circuit breakers are identified for the load served.

Final Inspection

Installation and operation of all plumbing fixtures. Water heater seismic strapping, pressure relief valve and piping. All gas-burning appliances connected to gas supply. All mechanical equipment in and operational. Clearances around panels. GFCI breakers or outlets tested. Smoke alarms. Handrails and guardrails installed with proper size, connections, and spandrel spacing. Fire Resistive construction for occupancy separation or rated wall construction sealed to maintain separation integrity including rated doors, and door jambs. Compliance with Title 24 standards, such as Energy and accessibility requirements, as required. Grading for drainage around structure.

Special Inspections

Scheduling an Inspection

Inspection Requests

Inspection requests can be made 24 hours a day by calling the City of Oceanside, Community Development Department, Building Division Inspection Request Line at: 760-435-3925.

Please note: You must call by 3:30 pm on a business day in order to receive a next business day inspection. Calls received after that time will be scheduled in two business days.

Multiple inspections for tract subdivisions may be requested by fax at: 760-435-3926

Inspection requests may be scheduled in person at the Building Division counter.

Inspection request by e-mail is not available at this time.